    System Topology Explanation

    2-Pole HSP-D40(500/600/800/1000V PV)

    Unilateral non-grounding: for floating PV strings, SPD suppresses surge between L+ and L-. Unilateral grounding: one PV busbar connected to PE, provides line-line & line-earth surge protection. Dual-stage protection: SPD in combiner box + SPD at inverter DC port, graded lightning protection.

    3-Pole HSP-D40(1500V PV only)

    Covers L+, L-, PE terminals, for 1500V utility solar farms. 3-way protection: L+↔L-, L+↔PE, L-↔PE. Works with DC switch & string fuses before inverter.

    Universal Rules

    • Graded protection: SPD at combiner box and inverter to lower residual voltage.
    • Series fuse required before each SPD to avoid thermal runaway.
    • 3P SPD mandatory for 1500V systems; 2P cannot be used on 1500V arrays.
    • PE cables must be short, low-resistance copper wire for fast surge discharge.